Not a valve selection or process safety tool Teaching and first-pass screening only, and not engineering advice. Do not use it to select, specify, verify or approve a valve for any real service. Open for the full scope limits.
What this tool actually solves
One flow coefficient, for steady single-phase flow of a clean Newtonian fluid through one valve at one operating point, by the published ISA-75.01.01 / IEC 60534-2-1 equations, using typical style coefficients rather than the coefficients of your valve.
Every one of those words is a restriction, and real services routinely break several of them at once.
Not checked, at all
- Noise and vibration: aerodynamic and hydrodynamic noise, sound power level, hearing exposure, and acoustically induced vibration, which fails piping by fatigue at welds and small-bore connections.
- The actuator: thrust or torque, shutoff and unbalance forces, spring rate, air supply, stroking speed, and the fail position on loss of signal or air.
- Shutoff: seat leakage class, tightness in service, and whether this valve is permitted to be an isolation point at all.
- Materials and mechanical rating: body and trim material, pressure and temperature rating, flange class, sour service, erosion, corrosion, galling and thermal shock.
- Velocity and energy limits: body outlet velocity, mass flux, trim energy limits, outlet erosion and pipe headloss.
- Trim life: cavitation damage rate, flashing erosion, and the difference between a service that runs for twenty years and one that destroys a plug in a month.
- Turbulence: the Reynolds number factor is not computed, so the turbulent regime every equation here assumes is never verified.
- The control loop: stability, tuning, dead band, hysteresis, stiction, resolution and dynamic response. The installed characteristic here is a teaching curve.
- Compliance: ASME B31.3, B16.34, PED, ATEX and hazardous area, fugitive emissions, and every code requirement of every jurisdiction.
A valve can satisfy every number on this page and still be the wrong valve for the service, and still fail in it.
Never use this for
- Sizing a pressure relief device, rupture disc, blowdown or depressuring path. That is API 520 / 521 work and this tool does not do it.
- Any safety instrumented function, protective layer or IEC 61511 SIL claim.
- Final valve selection or a purchase specification without the manufacturer's own sizing for the specific trim.
- Two-phase, flashing, slurry, polymerising or erosive service. Flashing is detected and refused; the rest are outside scope and are not detected.
- Anything needing a certified calculation or a PE stamp.
What it is checked against, and what that is worth
Seven worked examples from three independent publishers: the four annex examples in IEC 60534-2-1 itself and three from the Fisher handbook, covering liquid and gas, choked and unchoked, with and without reducers. The reducer loss coefficients reproduce the standard's printed values to the digit.
That establishes conformance to the published procedure. It does not establish that the procedure predicts the flow through your valve: the sizing equations are empirical correlations and the coefficients are flow-test measurements per trim, so ground truth for a real valve is a flow test.
Get a professional involved for
- Any service where failure means loss of containment, fire, explosion, toxic release or injury.
- Cavitating, flashing, high pressure drop, cryogenic, high temperature or lethal service.
- Anything a regulator, insurer or client will ask you to defend.
Service conditions
All pressures are absolute unless you switch the entry mode.
The coefficient the valve actually has, at the opening of interest. The result becomes the flow it will pass.
Fills the two pressures below from the vendored saturation table, 0.01 to 200 C. Outside that range the fields are left alone, since the curve is never extrapolated.
Absolute, at the inlet temperature. Leave it blank and the cavitation and flashing checks report that they did not run. Nothing is assumed to pass.
Needed with the vapour pressure to form FF, so leaving it blank stops the choke check specifically. A choked service sized without it comes out undersized.
Valve and piping
FL lies above 0 and at most 1; xT above 0 and below 1. These two are the entire choking and cavitation apparatus, so a value outside its definition is refused. Sizing with the checks quietly disabled is the failure this guards against.
Installed characteristic
Optional. Leave the system blank and the characteristic reports itself as not computed, with nothing assumed in its place.
Across the valve and the rest of the system together. A moody-chart result for the piping drops straight in here. It is cross-checked against the differential in the sizing case above, and a disagreement is reported.